The following procedure will restore factory defaults - Off Grid, Voltage Control mode, sealed battery voltage defaults.
Before restoring factory defaults it is highly recommended that the configuration settings be downloaded from the SP PRO (Configuration settings > Get SP PRO’s Configuration).
NOTE: For Firmware versions 8.14 and above, restoring factory defaults will require a configuration to be sent to the SP PRO before it will start.
- Set SP PRO in Idle mode with a long press of the ON button (ON LED will flash orange)
- Press and hold buttons B as shown, all LEDs will go off except AC Source, Transfer and AC Load if external AC supply is feeding through to AC loads.
- Whilst continuing to hold B, press C to select from following options -
- Green LEDs = Factory defaults
- No LEDs = Factory default settings will NOT be restored. No change to any setting
- Release all buttons, wait 10 seconds until LED display is stable.
- Factory Defaults as selected have been restored.
- Connect SP LINK and configure the SP PRO with the required configuration.
Additional Information
Visit the Selectronic: Knowledge Base or contact Selectronic via Customer Portal