SP PRO Generator Controller Wiring Guide
- Two Wire Run
- Two Wire Start / Stop
- Three Wire On / Start – Type 1
- Three Wire Start / Stop
- Three Wire Preheat / Run
- Three Wire Run / Stop
- Three Wire On / Start – Type 2
Wiring
Two Wire Run
This configuration is used when the generator controller requires two wires to be closed to start and Run and then opened to stop the generator.
Two Wire Start / Stop
This configuration is used when the generator controller requires two wires to be momentarily closed then opened to Start and run and the same again to Stop the generator.
Three Wire On / Start – Type 1
This configuration is used when the generator controller requires:
- One wire to be closed to a common wire to turn the controller On.
- Another wire to be momentarily closed then opened to the common wire to Start the generator.
- The generator is stopped when the On wire is opened.
Three Wire Start / Stop
This configuration is used when the generator controller requires:
- One wire to be momentarily closed then opened to a common wire to Start the generator.
- Another wire to be momentarily closed then opened to the common wire to Stop the generator.
Check the generator controller documentation to ensure that the Start Time, which is the time the wires remain closed for, is sufficient to be acted upon. Testing if the generator starts and stops correctly will determine if the default two seconds is suitable.
Three Wire Preheat / Run
- One wire to be momentarily closed then opened to a common wire to Preheat generator.
- Another wire closed to a common wire to Start and Run, and then opened to Stop the generator.
Check the generator documentation to ensure that the Start Time, which is the time the Preheat wire will remain closed for, is sufficient to allow engine starting in all conditions. The default of 2 seconds is unlikely to be suitable.
Three Wire Run / Stop
This configuration is used when the generator controller requires:
- One wire closed to a common wire Start and Run the generator.
- Another wire and momentarily closed then opened to a common wire to Stop the generator.
Check the generator controller documentation to ensure that the Start Time, which is the time the Stop wire will remain closed for, is sufficient to be acted upon. Testing if the generator stops correctly will determine if the default two seconds is suitable.
Three Wire On / Start – Type 2
This configuration is used when the generator controller requires:
- One wire to be closed to a common wire to turn the controller On.
- Another wire to be momentarily closed then opened to the common wire to Start the generator.
- The generator is Stopped when the On wire is opened and the Start disconnected from common.
Settings

Generator Controller

Generator Control Outputs

Generator Input Power Limit

Normal SoC Start and Stop

Signal Timing Graph

Commissioning
Troubleshooting




Additional Information