1. Compatibility and Requirements
SP
PRO
System | Primo
GEN24
SCERT |
SP PRO Series I single
phase | No |
SP PRO Series II single
phase | No |
SP PRO Series II multi
phase
(legacy) | No |
SP PRO Series II with
Advanced Comms Card, single, split or
three
phase
Powerchain. | Yes* |
SP PRO
Series 2i single, split or
three
phase
Powerchain. | Yes* |
- Each SP PRO Phase Manager can control up to five SCERT inverters and twice the total continuous rating of the SP PROs in the phase. This may be reduced further depending on your battery size or Electricity company allowances for On Grid systems.
- Phase Worker SP PROs cannot control SCERT
inverters.
- The Fronius SnapINverter and GEN24 cannot be connected to the same SP PRO phase.
- The SP PRO and Fronius GEN24
SCERT Managed AC coupling cannot be used with a Fronius Smart Meter.
- The SP PRO & Advanced Comm Card
must have firmware version 15.23 &
5.02 or higher.
- The Fronius
inverter must be Selectronic
Certified. Other Fronius inverters
will not
operate correctly.
On-Grid: The GEN24 Primo is compatible with SP PRO configured as On-grid AS/NZS 4777.2:2020, with the following models only - SPMC480-AU, SPMC481-AU, SPMC482-AU, SPLC1200 and SPLC1202.
- NOT compatible - SPMC240-AU, SPMC241-AU and SPMC1201.
For a Solar Hybrid (grid connected) system, the minimum capacity of the battery connected to the SP PRO varies depending on SP PRO model and the battery type. When the system is islanded (e.g. during a grid outage) the SP PRO will limit the output of the AC coupled solar based on the installed battery size.
- Off-grid: The GEN24 Primo is compatible with any SP PRO
Series 2i model or SP PRO Series II with
Advanced Comms
card, configured as Off-grid.
- For an Off-Grid system, the
minimum capacity of the battery
connected to the SP PRO
varies
depending on SP PRO model,
the battery type and the
total rating of all the connected
Fronius GEN24
SCERT inverters.
2. SP PRO Configuration
Check the firmware of the SP PRO
Tip: Performance Data > Download All will download the system logs in addition to a backup copy of the current configuration file.
Note: Do not update Fronius GEN24 SCERT firmware unless instructed by Selectronic.
3. AC Wiring
Fronius
AC Wiring guide for Off Grid
installation
Note: The system will not function correctly if the Fronius Primos are installed on the AC Source side of the SP PRO.
4. Communications Link
The communication link always starts at the
SP PRO, then daisy-chains to all Fronius
SCERTs in the system using RJ45 splitters.
Note: The RJ45 adapter cable comes connected to the Data Manager Connector within the Fronius SCERT.
5. GEN24 Configuration
Note: It is important that the Fronius inverter is connected to Solar.web so that Fronius may access the system remotely to perform problem diagnosis and resolution, and access data that is not obtainable through the SP PRO.
6. Network Configuration
Configuration of the network settings
allows for access to web
interface without using access point and
for integration to Solar.web.
7. Setting Time
Zone
8. Verification of Data Link
9. Verification of
Fallback Mode
When a Fronius SCERT
loses communications with the
SP PRO, the output of the
Fronius SCERT will drop to zero power after a few seconds.
Go to INFO > Readings menu on the front
display of the first Fronius SCERT and
check that the external limit (ext.
Lim.) drops to 0%.
10. Fronius SCERT “Backup Ready” Connection
The following steps are for when Selectronic Certified SCERT Fronius units are installed without an SP PRO,
A link must be fitted to the orange “Digital I/Os Connector” from the “V+” pin to IO “2” pin so that Fronius SCERTs can produce full power.
The country code must be set to AU – Australia.
- Access the Fronius web interface using Solar.start app, as instructed in Section 5.
- Login as Technician with the password provided with each Fronius GEN24.
- Navigate to “Safety and Grid Regulations” -> “Country Setup”
- Enter the code which may be obtained by contacting Fronius directly.
- Set the Country / Region to Australia and the Grid Code appropriately.
11. Export Power Limit
The following steps are for when Export Limitation is required for a Selectronic Certified SCERT Fronius units installed without an SP PRO. Refer to the Fronius instruction manual for details of export power limitations.
Set the country code as instructed in Section 10 but DO NOT fit the wire link.
- Access the Fronius web interface using Solar.start app, as instructed in Section 5.
- Login as Technician with the password provided with each Fronius GEN24.
- Navigate to “Safety and Grid Regulations” -> “Export Limitation”.
- Set the export limitation as required.
- Navigate to “Safety and Grid Regulations” -> “I/O Power Management”.
- Disable Rule 1.
- Save the settings.
If the system is later installed with an SP Pro this rule MUST be re-enabled.