Fronius Symo Fault Codes

 

Fronius Symo fault codes beginning with 1xx

 

Code
Description
Behaviour
Remedy
STATE 102
AC voltage too high
Following careful testing and when the grid conditions are within the permissible range again, the inverter will resume feeding energy into the grid.
Check grid connections: If this STATE code keeps recurring contact your solar power system installer.
STATE 103
AC voltage too low
STATE 105
AC frequency too high
STATE 106
AC frequency too low
STATE 107
AC grid outside the permissible limits
STATE 108
Stand alone operation detected
STATE 112
RCMU error

 

Fronius Symo fault codes beginning with 3xx


 

Code
Description
Behaviour
Remedy
STATE 301
Overcurrent (AC)
Short-term interruption while feeding energy into the grid due to over current in the inverter.
The inverter resumes with its startup routine.
Fault is rectified automatically; if this STATE code is displayed all the time: notify your local Fronius service partner.
STATE 302
Overcurrent (DC)
STATE 303
DC module over temperature
Short term interruption while feeding energy into the grid due to over temperature.
The inverter resumes with its startup routine.
Purge openings for cooling air and heat sink if necessary; fault is rectified automatically; if this STATE code keeps recurring contact your solar power system installer.
STATE 304
AC module over temperature
STATE 305
No power being fed in, despite closed relay
Short term interruption while feeding energy into the grid due to over temperature.
The inverter resumes with its startup routine.
fault is rectified automatically; if this STATE code keeps recurring contact your solar power system installer.
STATE 306
PV output too low for feeding energy into the grid
Short term interruption while feeding energy into the grid.
The inverter resumes with its startup routine.
Fault is rectified automatically; if this STATE code occurs when there is sufficient insolation (sunlight) contact your solar power system installer.
IMPORTANT! Due to the low level of insolation (sunlight) early in the morning and in the evening, the STATE codes 306 (LOW PV OUTPUT) and 307 LOW PV VOLTAGE) are displayed routinely at these times of day. These STATE codes do notindicate any kind of fault.
STATE 307
LOW PV VOLTAGE
DC input voltage too low for feeding energy into the grid
STATE 308
Intermediate circuit voltage too high
Short term interruption while feeding energy into the grid. The inverter resumes with its startup routine.
Fault is rectified automatically; if this STATE code is displayed all the time: notify your local Fronius service partner.
STATE 309
DC input voltage MPPT 1 too high
STATE 311
Polarity of DC strings reversed
STATE 313
DC input voltage MPPT 2 too high
STATE 314
Current sensor calibration timeout
Short term interruption while feeding energy into the grid. The inverter resumes with its startup routine.
Fault is rectified automatically; if this STATE code is displayed all the time: notify your local Fronius service partner.
STATE 315
AC current sensor erro
STATE 316
Interrupt Check fail
STATE 325
Overtemperature in the connection area
STATE 326
Fan 1 error
STATE 327
Fan 2 error

 

Fronius Symo fault codes beginning with 4xx

 

Code
Description
Behaviour
Remedy
STATE 401
No communication possible with the power stage set
The inverter will automatically attempt to connect again and, if possible, will resume feeding energy into the grid.
If the STATE code is displayed all the time contact your local Fronius Service Partner
STATE 406
AC module temperature sensor faulty (L1)
STATE 407
AC module temperature sensor faulty (L2)
STATE 408
DC component measured in the grid too high
STATE 412
Fixed voltage mode has been selected instead of MPP voltage mode and the fixed voltage has been set to too low or too high a value

If this STATE code persists contact your solar power system installer
STATE 415
Safety cut out via option card or RECERBO has triggered
The inverter is not feeding any energy into the grid.
If the STATE code is displayed all the time contact your local Fronius Service Partner
STATE 416
No communication possible between power stage set and control system
The inverter will automatically attempt to reconnect again and, if possible, will resume feeding energy into the grid.
STATE 417
Hardware ID problem
Update the inverter firmwarewith the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner.
STATE 419
Unique ID conflict
STATE 420
No communication possible with the Hybrid manager
STATE 421
HID range error
STATE 425
No communication with the power stage set possible
STATE 426-428
Possible hardware fault
STATE 431
Software problem
The inverter is not feeding any energy into the grid.
Carry out an AC reset (switch the AC circuit breaker off and on); update inverter firmware; if this status code is displayed all the time please contact your local Fronius Service Partner.
STATE 436
Functional incompatibility (one or more PC boards in the inverter are not compatible with each other, e.g. after a PC board has been replaced.
The inverter will automatically attempt to connect again and, if possible, will resume feeding energy into the grid.
Update the inverter firmwarewith the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner.
STATE 437
Power stage set problem
STATE 438
Functional incompatibility (one or more PC boards in the inverter in the inverter are not compatible with each other, e.g. after a PC board has been replaced)
STATE 443
Intermediate circuit voltage too low or asymmetric
The inverter is not feeding any energy into the grid.
If the status code is displayed all the time contact your local Fronius Service Partners.
STATE 445
– Compatability error (e.g. due to replacement of a PC board)
– invalid power stage set configuration
The inverter is not feeding any energy into the grid for safety reasons.
Update the inverter firmwarewith the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner.
STATE 447
Insulation fault
If this status code is displayed all the time: notify a local Fronius Service Partner
STATE 448
Neutral conductor not connected
STATE 450
Guard cannot be found
STATE 451
Memory error detected
The inverter will automatically attempt to connect again, and if possible, will resume feeding energy into the grid.
If the STATE code is displayed all the time: notify your local Fronius Service Partner.
STATE 452
Communication error between the processors
STATE 453
Grid voltage and power stage set are incompatible
STATE 454
Grid frequency and power stage set are incompatible
STATE 456
Anti-islanding function is no longer implemented correctly
STATE 457
Grid relay sticking or the neutral conductor ground voltage is too high
The inverter is not feeding any energy into the grid.
Check the grounding (the neutral conductor ground voltage must be less than 30V. If problem persists contact your local Fronius Service Partner.
STATE 458
Error when recording the measuring signal
Contact your local Fronius Service Partner.
STATE 459
Error when recording the measuring signal for the insulation test
STATE 460
Reference voltage source for the digital signal processor (DSP) is working out of tolerance
STATE 461
Fault in the DSP data memory
STATE 462
Error with DC feed monitoring routine
STATE 463
Reversed AC polarity, AC connector inserted incorrectly
STATE 474
RCMU sensor faulty
STATE 475
Solar panel ground fault, insulation fault (connection between solar panel and ground)
STATE 476
Driver supply voltage too low
STATE 480, 481
Functional incompatibility (one or more PC boards in the inverter are not compatible with each other, e.g. after a PC board has been replaced)
Update the inverter firmwarewith the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner.
STATE 482
Setup after the initial start-up was interrupted
Perform AC reset (turn AC circuit breaker off and on), complete startup.
STATE 483
Voltage UDC fixed on MPP2 string out of limits
Check the MPP settings; if the status code is displayed all the time contact your local Fronius Service Partner
STATE 485
CAN transmit buffer is full
Carry out an AC reset (turn AC circuit breaker off and on), if the STATE code continues to be displayed notify your local Fronius Service Partner.

 

Fronius Symo fault codes beginning with 5xx


 

Code
Description
Behaviour
Remedy
STATE 502
Insulation error on the solar panels
Warning message is shown on the display
If this STATE code keeps recurring, contact your solar power system installer.
STATE 509
No energy fed into the grid in the past 24 hours
Acknowledge STATE code; check whether all the conditions for the problem free feeding of energy into the grid have been met. If the STATE code is displayed all the time: look out for further STATE codes.
STATE 515
No communication with filter possible
If the status code is displayed all the time notify your local Fronius Service Partner.
STATE 516
No communication possible with the storage unit
Storage unit warning message.
STATE 517
Power derating caused by too high a temperature
When power derating occurs, a warning message is shown on the display
Purge cooling air openings and heat sink if necessary; fault is rectified automatically; if this STATE code keeps recurring contact your solar power system installer.
STATE 518
Internal DSP malfunction
Warning message on the display
If this STATE code keeps recurring contact your solar power system installer.
STATE 519
No communication possible with the storage unit
Storage unit warning message
STATE 520
No energy fed into the grid by MPPT1 in the past 24 hours
Warning message is shown on the display
Acknowledge status code; check whether all the conditions for the problem free feeding of energy into the grid has been met. If this STATE code keeps recurring contact your solar power system installer.
STATE 522
DC low string 1
Warning message on the display
STATE 523
DC low string 2
STATE 558, 559
Functional incompatibility (one or more PC boards in the inverter are not compatible with each other, e.g. after a PC board has been replaced)
Update the inverter firmwarewith the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner.
STATE 560
Derating caused by over-frequency
This STATE code is displayed when the grid frequency becomes excessively high. The inverter will then reduce its output. The status indicator will continue to be displayed until the inverter has returned to normal operation.
As soon as the grid frequency is back within the permissible range and the inverter has returned to normal operation, the fault is rectified automatically. If this STATE code keep recurring contact your solar power system installer.
STATE 564
Functional incompatibility (one or more PC boards in the inverter are not compatible with each other, e.g. after a PC board has been replaced)
Warning message on the display
Update the inverter firmwarewith the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner.
STATE 566
Arc detector switched off (e.g. during external arc monitoring)
The STATE code is displayed every day until the arc detector is reactivated.
No error
Confirm status code by pressing ‘Enter’.
STATE 567
Grid Voltage Dependent Power Reduction is active
This state code is a warning informing you that the Grid Voltage Dependent Power Reduction mode (GVDPR or Volt – Watt mode) has been activated and the inverter will continue to operate with reduced power output. This is because the grid voltage has exceeded 250Vac and the GVDPR has been enabled to try to reduce the voltage rise at the inverters terminals. This mode must be enabled by default in accordance with the latest Australian Standards.
Acknowledge status code; if this STATE 567 code keeps recurring contact your local solar power system installer.

Fronius Symo fault codes beginning with 6xx


 

Code
Description
Behaviour
Remedy
STATE 601
CAN bus is full
The inverter is not feeding any energy into the grid.
Update the inverter firmwarewith the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner.
STATE 603
AC module temperature sensor faulty (L3)
The inverter will automatically attempt to connect again and, if possible, will resume feeding energy into the grid.
If this STATE code keeps recurring contact your solar power system installer.
STATE 604
DC module temperature sensor faulty
STATE 607
RCMU error
The inverter is not feeding any energy into the grid.
Reset status code by pressing ‘Enter’. The inverter resumes the feeding of energy into the grid; if the status code keeps appearing, check the complete solar system for damage.
STATE 608
Functional incompatibility (one or more PC boards in the inverter are not compatible with each other, e.g. after a PC board has been replaced)
Update the inverter firmwarewith the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner.



Fronius Symo fault codes beginning with 7xx  



Code
Description
Behaviour
Remedy
STATE 701-716
Provides information about the internal processor status
Warning message is shown on the display
If the STATE code is displayed all the time notify your local Fronius Service Partner.
STATE 721
EEPROM has been re-initialised
Acknowledge STATE code; If the STATE code is displayed all the time contact your local Fronius Service Partner
STATE 722-730
Provides information about the internal processor status
If the STATE code is displayed all the time contact your local Fronius Service Partner
STATE 731
Initialisation error – USB flash drive is not supported
Check or replace USB flash drive. Check the file system on the USB flash drive. If the STATE code is displayed all the time notify your local Fronius Service Partner.
STATE 732
Initialisation erro – Over current on USB stick
STATE 733
No USB flash drive connected
Connect or check the USB flash drive. If STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 734
Update file not recognised or not present
Check update file (e.g. for correct file name). If STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 735
Update file does not match the device, update file too old
Warning message appears on the display, update process is interrupted.
Check the update file with the latest firmware here; if the STATE code is displayed all the time after the firmware update contact your local Fronius Service Partner.
STATE 736
Write or read error occurred
Warning message is shown on the display
Check USB flash drive and the data contained on it or replace USB flash drive.
Never unplug a USB flash drive if the ‘Data Transmission’ LED is still flashing or lit.
If the STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 737
File could not be opened
Remove and then reinsert USB flash drive; check or replace USB flash drive
STATE 738
Log file cannot be saved (e.g. USB flash drive is write protected or full)
Create storage space, remove write protection, check or replace USB stick if necessary.
If STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 740
Initialisation error-error in file system on USB flash drive
Check USB flash drive; reformat on PC for FAT12, FAT16 or FAT32.
STATE 741
Error during recording of logging data
Remove and then reinsert USB flash drive; check or replace USB flash drive
STATE 743
Error occurred during update process
Repeat the update process, check USB stick. If STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 745
Update file corrupt
Warning message appears on the display, update process is interrupted.
Re-download update file. If STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 746
Error occurred during update process
Wait for 2 minutes, then start the update again. If STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 751
Time lost
Warning message is shown on the display
Reset the time and date on the inverter. Check update file (e.g. for correct file name). If STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 752
Real Time Clock module communication error
STATE 753
Internal error: Real Time Clock module is in emergency mode
Time may be inaccurate or lost (feeding energy into the grid normal)
STATE 754-755
Provides information about the processor status
Warning message on the display
If STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 757
Hardware error in the Real Time Clock module
Error message is shown on the display; the inverter is not feeding any energy into the grid.
STATE 758
Internal error: Real Time Clock module is in emergency mode
Time may be inaccurate or lost (feeding energy into the grid normal).
Reset time and date on the inverter
STATE 760
Internal hardware error
Error message is shown on the display.
If STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 761-765
Provides information about the internal processor status
Warning message is shown on the display.
STATE 766
Emergency power de-rating has been activated
Error message is shown on the display.
STATE 767
Provides information about the internal processor status
Warning message is shown on the display.
STATE 768
Different power limitation in the hardware modules
STATE 772
Storage unit not available
STATE 773
Software update group 0 (invalid country setup)
STATE 775
PMC power stage set not available
Warning message is shown on the display.
Press ‘Enter’ key to acknowledge error. If STATE code is displayed all the time contact your local Fronius Service Partner.
STATE 776
Invalid device type
STATE 781-794
Provides information about the internal processor status
Warning message is shown on the display.
If STATE code is displayed all the time contact your local Fronius Service Partner.