Installation Note: IN0053 - Rev 07

Introduction

The SP PRO Managed AC Coupling provides a method of linking the ABB UNO Selectronic Certified (SCERT) inverters to the SP PRO via the AC Load supply so that regardless of whether the grid or a generator is connected, the SP PRO can manage and control the ABB UNO string inverters.

Each SP PRO can manage a maximum of five ABB UNO inverters by commanding each inverter to output the right amount of power that is needed simultaneously to supply the load, export any excess and maintain the battery bank at any particular point in time. This is done via a communications link which also serves to retrieve all the operational data for display and logging by the SP PRO.

NOTE: This document needs to be read in conjunction with the SP PRO Instruction Manual and any relevant ABB UNO Instruction Manuals.

Image Placeholder

See Appendix II for ABB PVI Managed AC Coupling installation instructions.

Image Placeholder

This document applies for SP PRO Series 2i. SP PRO Series 1 is not supported.


Important information

  • ABB UNO can only be configured while minimum 200Vdc is applied to the solar inputs.

  • The ABB UNO-DM PLUS-B or PLUS-Q  inverters can be installed with any existing ABB Selectronic Certified inverter.

  • For Wireless RS485 communication, please order Wireless RS485 link kit (Order Code: 005316) for: ABB UNO-DM PLUS-B or PLUS-Q (see Appendix I)

  • To extend the range of the wireless devices, please order the Patch Antenna (Order code 004810)


Installation check list

The following list summarises the steps taken to set up an ABB UNO-DM in a Managed AC Coupled system. Once the system has been installed, use the following list to check off that each step has been completed.

  • Install SP PROs as per manual
  • Install and configure batteries
  • ABB UNO must be Selectronic Certified
  • SP PRO firmware requirement - 12.20 or higher
  • ABB UNO AC Wiring
  • Communications Link (RS485)
  • Configure Additional Settings in SP PRO
    • NOTE: The SP PRO must be configured via SP LINK "Site Configuration Wizard" before configuring ABB UNO
  • Configure the ABB UNO Q or QU - No front screen on ABB
  • Configure the ABB UNO - Front screen
  • Test system function

The Overview

The diagram below shows a managed AC coupled system with five ABB UNOs.

Image Placeholder

System Requirements

To successfully install an SP PRO ABB managed system, there are particular requirements that need to be met:

  • SP LINK Site Configuration Wizard must be used to verify:

    • Combined maximum ABB AC output

    • Battery bank size

  • SP PRO must have firmware version 10.01 or higher.

  • All ABB UNOs must be Selectronic Certified.

  • Maximum of five ABB UNOs per SP PRO.

  • SP PRO Series 2i


Minimum Battery Capacity for Solar Hybrid & Off Grid Systems
Each application will have a minimum battery capacity and a maximum allowable PV, please refer to the battery manufacturer’s data sheet as well as the guidance given in the SP LINK Site Configuration Wizard.

NOTE:

  • For a Solar Hybrid (grid connected) system, the minimum battery capacity that must be connected to the SP PRO varies depending on SP PRO model. When the system is islanded (e.g. during a grid outage) the SP PRO will limit the output of the AC coupled solar based on the actual installed battery size.
  • For an Off-Grid system, the minimum battery capacity that must be connected to the SP PRO varies depending on SP PRO model, an overriding minimum battery capacity and the combined maximum ABB UNO AC Output.


SP PRO Firmware Requirements

  • SP PRO Software Version 12.20 or higher is required. To check software revision run SP LINK, connect to the SP PRO and go to Data View > Inverter Details > SP PRO Revision and Software Version
Image Placeholder

Data View  Inverter Details screen

  • The SP PRO must be Series 2i

NOTE:

  • Older revisions of firmware must be updated to firmware revision 12.20 or higher.
  • Do not change any configuration settings until firmware is updated.


ABB UNO Must be Selectronic Certified
The ABB UNO must be Selectronic Certified. Other ABB UNOs will not operate correctly with the SP PRO in a managed AC coupled configuration.

Image Placeholder


Installation

The SP PRO and ABB UNOs must be installed as per their respective installation instructions. Particular instructions directly related to Managed AC Coupling are listed below.

It is good practice to number each ABB UNO from 1 up to 5 so that each inverter can be easily referenced within SP LINK.

In a multiphase system, label each ABB UNO on L1, from L1-1 to L1-5. Do likewise for each of the ABB UNOs connected to L2, from L2-1 to L2-5 and so on.

ABB UNO AC Wiring

The ABB UNO AC output wiring must be connected to the AC Load terminals of the SP PRO in accordance with local wiring rules for correct operation.

Image Placeholder

ABB AC Wiring guide for Grid connected installation


Image Placeholder

ABB UNO AC Wiring guide for Off Grid installation

NOTE: The system will not function correctly if the ABB UNOs are installed on the AC Source side of the SP PRO.


Communications Link (RS485)

The communication link always starts at the SP PRO and links to each of the ABB UNOs in a daisy chain arrangement.

Image Placeholder
SP PRO Connections (inside unit)  RS485 Port 2 RJ45 connector to RJ45 Adapter.
RJ45 Adapter to ABB UNO RS485 connector.


RS485 Connection to First ABB UNO

Using the supplied CAT5 network cable, connect one end to the Advanced Communications Card RS485-2 connection on the SP PRO. At ABB UNO 01 (Address# 02), connect the CAT5 cable to the RS485 adapter cable, and terminate the adapter into the ABB communications board.

NOTE: For wireless RS485 communication (Order code: 005316) please refer to Appendix I.

Image Placeholder

NOTE: To terminate the RS485 adapter cable into ABB communications board, push down the black tabs and insert the bootlace pinned wires into the board as follows.

Image Placeholder

ABB UNO Connections (inside unit)  RS485 Adapter Wires terminated into the ABB communications board


Wire Colour
ABB Connector Label
Red
- T/R
Black
+ T/R
White
RTN

Set the 120Ω termination to ON if only a single unit is connected to the SP PRO. If more than one unit is connected, follow the instructions on the next page.


Connecting ABB UNO link between Inverters 02 (Address# 03) to 05 (Address# 06)

The following configuration outlines the connection for multiple ABB UNOs to the first ABB UNO (ABB UNO 01). If only a single ABB UNO is installed, skip to the next section: (CONFIGURATION  ADDITIONAL SETTINGS)

The ABB UNO RS485 is designed to interface with multiple ABB UNOs in a daisy chain arrangement as shown below.

When looping an ABB UNO to another ABB UNO, the termination jumper must be set to “OFF” (away from ON). For the last ABB UNO, the termination jumper must be set to “ON”.

Image Placeholder


Configuring Additional Settings in SP PRO

The Site Configuration wizard (in SP LINK 9.9 or higher) must be used to configure the SP PRO settings. Using the wizard will ensure all SP PRO settings are compatible with the managed AC coupled system.

The SP PRO must be configured before any of the ABB UNOs are energised.

The ABB UNOs RS485 must be set sequentially from Address# 02. (See “ABB UNO Configuration” section).

Go to the SP LINK tab Configuration Settings > System, and make sure that:

  • String Inverter is set to ABB Solar.

  • Number of Devices is set to the number of ABB UNOs installed in the system.

Image Placeholder
SP LINK > Configuration Settings > System tab

In the example used above, two ABB UNOs are connected to the SP PRO.


ABB UNO Q Configuration (NO DISPLAY)

NOTE: If your ABB UNO has a display, go to ABB UNO Configuration (DISPLAY).

The settings listed below are required to be configured in each ABB UNO Q in order for the system to operate correctly. Each ABB UNO must be set to an RS485 node address from 2 to 6 as appropriate.

  • Isolate the AC and connect the DC supply to the ABB UNO(s) and ensure that the DC supply (Minimum 200 VDC) is present at the ABB UNO.

  • Connect the WiFi antenna to the bottom of the ABB UNO

  • Follow the instructions in the ABB quick installation guide to connect your mobile phone to the ABB UNO inverter and follow the instructions on the screen until you reach the dashboard screen.

  • Select the menu, communications option then RS485.

Image Placeholder     Image Placeholder     Image Placeholder

  • Once the RS485 Screen is displayed enter the details as shown above
    • If only one ABB UNO is installed then the RS485 node address must be set to 2.
    • If more than one ABB UNO is installed then the RS485 node address must be allocated sequentially starting from 2.
    • Once details are entered then select the Save button to save the configuration.

NOTE: Do not skip any address numbers in the sequence.


Continue to section “System Commissioning – Additional Tests”


ABB UNO Configuration (DISPLAY)

The settings listed below are required to be configured in each ABB UNO in order for the system to operate correctly.

Each ABB UNO must be set to an RS485 address from 2 to 6 as appropriate.

  • Isolate the AC and connect the DC supply to the ABB UNO(s) and ensure that the DC supply (Minimum 200 VDC) is present at the ABB UNO

  • When the ABB UNO is powered for the first time, select the “Nation” of installation. For Australia and New Zealand select “AS 4777” and press the ENTER key once and to save the setting, hold the ENTER key for 5 seconds, the ABB UNO will reset

  • Step through the initial stages of commissioning the inverters date and time, current input mode, Grid select, country select, etc, until the following is displayed on the screen.

Image Placeholder

NOTE: When an ABB UNO is powered without the AC, “Missing Grid “will be displayed on screen.

  • Once the display is active on the ABB UNO, enter the main menu. To enter main menu, press the ESC button once, then using the DOWN key, scroll to System and press ENTER. The ESC is also used to escape back to the previous menu or to edit previous digits
Image Placeholder

  • Scroll to Settings and press ENTER.
Image Placeholder
  • To access Settings, a passcode is required. By default, 0000 is the passcode or by pressing the ENTER key four times to access the setting option. Use ENTER key to confirm an action or to access submenus
Image Placeholder

  • Scroll to Set RS485 Com and press ENTER.
Image Placeholder

  • Scroll to Set Port and press ENTER.
Image Placeholder

  • Scroll to Address RS485 and press ENTER.
Image Placeholder

    • If only one ABB UNO is installed then the address must be set to 2/63.
    • If more than one ABB UNO is installed then the address must be allocated sequentially starting from 2/63 (i.e. first ABB UNO = 2/63, second ABB UNO = 3/63, third ABB UNO = 4/63 etc).
    • Once the “Inverter Number” is selected, press the ENTER button to configure and return to the “Set Port” menu.
NOTE: Do not skip any address numbers in the sequence.

  • Scroll to Protocol and press ENTER.
Image Placeholder

    • Scroll DOWN and select Aurora (slave) and press the ENTER button to configure and return to the “Set Port” menu.
  • Press the ESC button five times to return to the main display.
Image Placeholder

  • If there are multiple ABB UNOs installed, repeat for all others.
  • When all is configured, the ABB UNO display screen will cycle through the amount of energy currently fed automatically.

Continue to section “System Commissioning – Additional Tests”



System Commissioning  Additional Tests

In addition to the normal system testing that would be performed, the following additional tests must be performed as detailed below.

NOTE: Make sure that only DC is connected at this stage.

Communications Link Verification
The correct operation of the ABB Managed AC Coupling relies on the Communications Link. It is vital that the communications link (RS485) connection has been setup correctly before operating the AC coupled system.

Image Placeholder

  • Check that all the RS485 connections have been connected correctly.

  • Isolate the AC and connect the DC supply to the ABB UNO. Make sure that the DC supply is pressent at the ABB UNO and its display is on.

  • Using SP LINK, connect to the SP PRO. In the Data View > Now tab there should be a model number displayed for each of the installed inverters.


The communication link may be further tested using the AC Solar Link Test found in SP LINK under the Service Settings tab.

  • In the Service Settings tab click the Reset Counters button.

Image Placeholder

  • Wait 2 minutes and check that the error count remains at zero for all the connected ABB UNOs. (An error count of 5 or less per minute is acceptable, but in this case, it is good practice to check the wiring and that the termination resistors are set correctly in the SP PRO and ABB UNO.
Once the Communications link has been verified for each ABB UNO, the AC feeds to each ABB UNO can be switched on and full system testing and verification can be performed.

Testing the Failsafe on the RS485 Link

Once the system is operational, unplug the RS485 communications link from the SP PRO to the ABB UNOs. Wait 1 minute and check that the output of each of the ABB UNOs has dropped to approximately 0.1kW.



Appendix I: Wireless RS485 for ABB UNO-DM Link


Introduction

This instruction will show how to install the Wireless RS485 link Kit (Order code 005316).

This details the additional steps needed to install a Wireless RS485 link into a SP PRO ABB UNO- DM Managed AC Coupled system.

Important information

  • This document needs to be read in conjunction with:

    • SP PRO AU Instruction Manual

    • Relevant ABB UNO-DM Installation Manual

  • SD1100 RS485 Wireless adaptors are powered from the supplied plug packs. The plug packs must be connected to the same AC power circuit as the connected ABB UNOs. This is normally the AC load side of the SP PRO.

  • To extend the range of the wireless devices, please order the Patch Antenna (Order code 004810).


Additional information

Selectronic web site: http://www.selectronic.com.au or contact the Selectronic team.


Legend to diagrams in this document

Image Placeholder


Overview

The diagrams below illustrate the options for single phase managed AC coupled system with ABB UNO-DM inverters.

Image Placeholder

Figure 1: Single phase system with one wireless ABB UNO-DM

Image Placeholder

Figure 2: Single phase system with multiple wireless ABB UNO-DM


Installing a separate pair of wireless RS485 devices on each phase

The diagram below shows a three-phase managed AC coupled system with three ABB UNOs per phase. A separate pair of Wireless RS485 link Kit (Order code 005316) must be used for each phase.

NOTE: When using multiple Wireless RS485 device pairs use Patch Antennas on each of the devices at the local end of the system (SP PRO end). This will reduce the interference between devices. Keep patch antennas separated by a minimum of 300mm.

Image Placeholder

Figure 3: Overview of three phase system using Wireless RS485


Wireless link restrictions

The wireless link uses the same frequency band as Wi-Fi and Bluetooth (2.4GHz). Any obstructions between the two devices or interference from other devices using the same frequency band (other blue tooth or Wi-Fi devices) will have a significant impact on their range.

To achieve the maximum range of 200m there must be line of sight between the two devices and no interference. As a rule of thumb, each obstruction that is equivalent to a stud wall will reduce the distance by about 20%. Mud brick walls, double brick or concrete walls will have a much larger impact on the range.

Any obstruction from the landscape such as levy banks, hills or undulation land will totally block the signal and the wireless link will not work.

If more than one wireless link is required within the same installation (such as a three-phase system or multiple remote sites) then the interference between the devices will further reduce the distance. In this case it is recommended that a patch antenna be used on all local Wireless devices.

Extending the Wireless Range

If the required distance is longer than the specified 200m clear line of site, or there are multiple devices being used then the range of the devices can be extended by replacing the dipole antenna with a “patch” antenna. The table 1 below gives an indication of the expected range when using a combination of dipole and patch antennas:



Table 1: Maximum “Line of site” distance between Wireless RS485 device pairs.

Local Wireless device antenna
Remote wireless device antenna
Max distance, one pair of devices (line of sight)
Max. distance, multiple pair of devices (line of sight)
Dipole (supplied)
Dipole (supplied)
200m
Not recommended
Patch  Optional (stock code 004810)
Dipole (supplied)
300m
150m
Patch  Optional (stock code 004810)
Patch  Optional (stock code 004810)
500m
250m
Image Placeholder
Optional Patch Antenna to extend the range of the wireless devices
(Selectronic Order Code 004810)

NOTE: Patch Antenna is directional and must be mounted in a fixed position that is directly facing the antenna of the other wireless device.


Installation

NOTE: If you have been supplied with an “AC Coupled Interface PCA” and have an old communications card, please refer to Appendix III for instructions on how to configure RS485 communications.

The communication link starts at the SP PRO and links to the MASTER SD1100 RS485 Wireless adaptor.

Image Placeholder
SP PRO Connections (inside unit)
RS485 Port 2 RJ45 connector to RJ45 Adapter to ABB UNO RS485B connector


Wireless connection to ABB UNO-DM

Using the supplied ‘CAT5’ network cable connect one end to the SLAVE SD1100 RS485 Wireless adaptor. At ABB UNO 01 (Address# 02), connect the CAT5 cable to the RS485 adapter cable, and terminate the adapter into the ABB communications board.

NOTE: SD1100 RS485 Wireless adaptors are powered from the supplied plug packs. The plug packs must be connected to the same AC power circuit as the connected ABB UNOs. This is normally the AC load side of the SP PRO.

Image Placeholder

NOTE: To terminate the RS485 adapter cable into ABB communications board, push down the black tabs and insert the bootlace pinned wires into the board as follows.

Image Placeholder     Image Placeholder
ABB UNO Connections (inside unit)  RS485 Adapter Wires terminated into the ABB communications board


Wire Colour
ABB Connector Label
Red
- T/R
Black
+ T/R
White
RTN

The last ABB UNO of the daisy chain must be terminated provided jumper at the pins marked 120Ω TERM. must be placed in the ON position as shown.

Image Placeholder

NOTE: When connecting multiple ABB UNOs together, the terminating jumper must be set to OFF 120Ω TERM for all ABB UNO except the last inverter of the daisy chain (ON).

Power for the Wireless RS485 devices

The RS485 devices are powered from the supplied plug packs. The plug packs must be connected to the same AC power circuit as the connected ABB UNOs. This is normally the AC load side of the SP PRO.

Image Placeholder

Figure 5: SD1100 RS485 Wireless adaptor power connection



Appendix II: SP PRO ABB PVI Managed AC Coupling


Introduction

This section details the additional steps needed to install the managed AC Coupling system for ABB PVI-3.0/3.6/4.2-TL-OUTD and ABB PVI-5000/6000-TL-OUTD string inverters to the SP PRO.

NOTE: Installation note applies for SP PRO Series II Rev21 and above.


Image Placeholder

NOTE: ABB can only be configured while minimum 200Vdc is applied to the solar inputs.


The Overview

The diagram below shows a managed AC coupled system with five ABB PVI inverters.


Image Placeholder


System Requirements

To successfully install an SP PRO ABB PVI managed system, there are particular requirements that need to be met.

  • This installation document is applicable to SP PRO Series 2 (revision 21 or greater) inverters only with 8.0 Firmware or greater.

  • Combined maximum AC output of all the connected ABB UNOs must not exceed twice the continuous rating of the SP PRO (Except for SPLC1202 which is 35kW).

  • Battery bank must be sized to suit the SP PRO model and the combined maximum AC Output power of the ABB UNOs.

  • SP PRO must have firmware version 8.0 or greater.

  • All ABB UNOs must be Selectronic Certified (Selectronic signage on front access cover).

  • Maximum of 5 ABB UNOs per SP PRO


SP PRO Requirements

  • The SP PRO units’ revision must be 21 or later (series 2).
  • SP PRO Software Version 8.0 or later is required. To check software revision run SP LINK, connect to the SP PRO and go to Data View > Inverter Details > SP PRO Revision and Software Version
Image Placeholder

Packaging Label indicating Revision: 21


Image Placeholder
Data View > Inverter Details screen

  • Older revisions of firmware must be updated to firmware revision 8.0 or later.
  • Do NOT change any configuration settings until firmware is updated.

NOTE: Selectronic web site: http://www.selectronic.com.au for latest SP PRO firmware and Tech Note 34 SP PRO Firmware Update Procedure.

ABB Must be Selectronic Certified

The ABB UNO must be Selectronic Certified. Other ABB UNOs will not operate correctly with the SP PRO in a managed AC coupled configuration.

Image Placeholder


Installation

The SP PRO and ABB UNOs should be installed as per their respective installation instructions. Particular instructions directly related to Managed AC Coupling are listed below.

It is good practice to number each ABB UNO from 1 up to 5 so that each inverter can be easily referenced within SP LINK. In a three phase AC coupled system label each ABB UNO L1-1 to L1- 5 for the ABB UNOs connected to SP PRO L1, L2-1 to L2-5 for those connected to L2 and so on.

NOTE: The address numbers programmed into ABB solar inverters start from 2 and go up to 6 (instead of 1 to 5). When viewing Data in SP Link, inverter #1 is connected to ABB UNO address 2, inverter #2 is connected to ABB UNO address 3 etc.


ABB AC wiring

The ABB AC output wiring must be connected to the AC Load terminals of the SP PRO in accordance with local wiring rules for correct operation.

Image Placeholder

ABB AC Wiring guide for Grid connected installation


Image Placeholder

ABB AC Wiring guide for Off Grid installation


NOTE: The system will NOT function correctly if the ABB UNOs are installed on the AC Source side of the SP PRO.


Communications Link (RS485)

The communication link always starts at the SP PRO and links to the AC Coupled Interface PCA, then connects to all the ABB UNOs in a daisy chain arrangement and finishes at the last ABB UNO. The ABB UNO link is used to connect subsequent ABB UNOs ON the same phase as the SP PRO. Do not connect ABB UNOs on different phases together.

To install the AC Coupled Interface PCA, remove the bottom two screws from the Expansion Card and replace them with the provided 2x stand offs. Then mount the AC Coupled Interface PCA to the Expansion Card inside the SP PRO close to the Serial Communication PCA as illustrated.

Image Placeholder

  • Connect the RJ45 Connector lead from the AC Coupled Interface PCA To RS485 Port 2” to the SP PRO Serial Communication PCA RS485 Port 2.

  • Connect the second RJ45 lead from the AC Coupled Interface PCA To ABB AC Coupled Inverter to the ABB UNO RS485 connector (see section “RS485 Connection to first ABB UNO”).

  • Connect the AC Coupled Interface PCA power loom (12V) from AC Coupled Interface PCA 12V DC Power J4 to the SP PRO Serial Communication PCA 12V connector.

NOTE: Do not connect any RJ45 leads to the AC Coupled Interface PCA To Other AC Coupled Inverters connector as the pin out is different to the ABB UNO connection.


ABB UNO Communication link to SP PRO Communication Card

Image Placeholder
SP PRO Connections (inside unit)
RS485 Port 2 RJ45 connector to AC Coupled Interface PCA (Sergio) and to ABB UNO RS485B connector

ABB PVI-3.0/3.6/4.2-TL-OUTD Series RS485 Connections

Image Placeholder

ABB PVI-3.0/3.6/4.2-TL-OUTD Series RS485 Connections (inside unit)  RJ45 connectors


On the ABB UNO there are two RJ45 sockets allowing “looping through” of the wiring to additional inverters. Either connection point is suitable.

When looped to another ABB UNO, the termination switch should be set to OFF (away from ON). For the last ABB UNO on the Communications Link (RS485) (or when only one ABB UNO is used), the termination switch must be set to ON.

Image Placeholder

ABB PVI-5000/6000-TL-OUTD Series

Image Placeholder

ABB PVI-5000/6000-TL-OUTD Series RS485 Connections (inside unit)  RJ45 connectors


On the ABB UNO there are two parallel sets of RJ45 connections allowing “looping through” of the wiring to additional inverters. Either connection point is suitable.

When looped to another ABB, the termination switch should be set to OFF (away from ON). For the last ABB UNO on the Communications Link (RS485) (or when only one ABB UNO is used), the termination switch must be set to ON.

Image Placeholder

Configuration  Additional Settings

It is recommended that the Site Configuration wizard in the Easy Start Guide (in SP LINK 8.0 and above) be used to configure the SP PRO settings. Using the wizard will ensure all the SP PRO settings are compatible with the manage AC coupled system.

The settings detailed below will be set when the Site Configuration Wizard is used to configure the SP PRO. Only the additional settings required to enable ABB Managed AC Coupling are shown. The remainder of systems settings will be set by the Site Configuration Wizard.

The SP PRO must be configured before any of the ABB UNOs are energised. The AC coupled failsafe system in the SP PRO is only enabled when the correct ABB configuration has been programmed into the SP PRO.

The ABB UNOs must be appropriately addressed to ensure correct communications (see “ABB Port Configuration” section).


Settings That Are Set by Site Configuration Wizard
In SP Link > Configuration Settings > System, the follow settings will be set:

  • Managed AC Coupled Link, String Inverter is set to ABB Solar.
  • Number of ABB UNOs connected is set to the number of ABB UNOs installed in the system.
Image Placeholder

SP LINK - Configuration Settings  System tab


NOTE:

  • Port 2 Communication settings will not be available once ABB Communication port has been enabled.
  • The ABB UNOs numbering starts from 2 to 6 instead of 1 to 5 when creating a communication link to SP Link e.g. inverter 1 in SP Link is connected to ABB UNO address 2, inverter 2 in SP Link is connected to ABB UNO address 3 etc.

In the example used above, there are two ABB UNO connected to the SP PRO.


ABB Port Configuration

The settings listed below are all that is required. Each ABB UNO must be set to an inverter address from 2 to 6 as appropriate.

NOTE: The ABB UNOs numbering starts from 2 to 6 instead of 1 to 5 when creating a communication link to SP Link e.g. inverter 1 in SP Link is connected to ABB UNO address 2, inverter 2 in SP Link is connected to ABB UNO address 3 etc.

  • Isolate the AC and connect the DC supply to the ABB UNO(s) and ensure that the DC supply (Minimum 200Vdc) is present at the ABB UNO.

  • When the ABB UNO is powered for the first time, select the “Nation” of installation. For Australia and New Zealand select “AS 4777” and press the ENTER key once and to save the setting, hold the ENTER key for 5 seconds, the ABB UNO will reset.

Image Placeholder

Image Placeholder

NOTE: When an ABB UNO is powered without the AC, “Missing Grid “will be displayed on screen.

Image Placeholder


  • Once the display is active on the ABB UNO, enter parameter settings mode. To enter settings mode, press the ESC button to access the main menu, then using the DOWN key, scroll to Setting and press ENTER. The ESC is also used to escape back to the previous menu or to edit previous digits.
  • Use the UP and DOWN keys to scroll through the various menu items in settings. The menu is continuous. When the end is reached, the display automatically returns to the first item. The UP/DOWN keys are used to scroll menu options or to shift numerical scales in ascending/descending order.
  • To access Settings, a passcode is required. By default, 0000 is the passcode or by pressing the ENTER key four times to access the setting option. Use ENTER key to confirm an action or to access submenus.
  • Scroll to Address setting and press ENTER.
Image Placeholder

    • If only one ABB UNO is installed then the address must be set to 2.
    • If more than one ABB UNO is installed then the address must be allocated sequentially starting from 2 (i.e. first ABB = 2, second ABB = 3, third ABB = 4 etc).
    • Once the Address is selected, press the ENTER key to configure and return to the Setting menu.
Image Placeholder

  • NOTE:
    • The ABB UNO address starts from 2 to 6, where inverter 1 in SP Link is connected to ABB UNO Address 2, i.e. ABB UNO 1 address 2 = inverter 1 SP Link, ABB UNO 2 address 3 = inverter 2 SP Link, ABB UNO 3 address 4 = inverter 3 SP Link etc.
    • Do Not skip any address numbers in the sequence when using multiple ABB UNOs.
  • Scroll to Remote Control setting and press ENTER.
Image Placeholder

    • Set the ABB UNO Remote Control to Enable, this will allow the ABB UNO to disconnect through the control signal.
    • Once the Remote Control is enabled, press the ENTER key to configure and return to the Settings menu.
NOTE: The PVI-6000-TL-OUTD Remote Control setting contains an extra sub menu Three Phase Unbalanced, when prompted, press the ESC key to return to Enable/Disable Remote Control and select Enable.

  • Scroll to the Power Reduction setting and press ENTER.
NOTE: ABB UNOs compliant with the AS/NZS 4777.2-2015 will not contain the Power

Reduction setting in the inverter.

Image Placeholder

    • The ABB UNO is set to 100% as default, use the UP key to set the Power Reduction to 0.0%.
    • Once the Remote Reduction is selected, press the ENTER key to configure and return to the Settings menu.
NOTE: Do not go back into the Power Reduction setting once it is set to 0% otherwise the display will show 100% even though the setting was set to 0%. This is normal. The 0% can be verified by the commissioning test Testing the Failsafe on the RS485 Link.

  • Press the ESC key once to return to the main menu. The ABB UNO may perform an automatic reset to configure the changes made.
  • If there are multiple ABB UNOs installed, repeat for all others.
  • When all is configured, the ABB UNO display screen will cycle through the main menu automatically. To stop the menu from cycling, press and hold the ENTER key until a lock appears at the top right-hand corner of the display screen.
    • To check that the ABB UNO is under power control, use the DOWN key to approach the following menu screen, make sure a percentage is displayed on the display indicating that the inverter is controlled by the SP PRO.
Image Placeholder

    • The Percentage Power may be displaying less than 100% even though no power limiting is required. This is because the SP PRO intelligently uses predictive algorithms to determine the optimum value based on the available solar input to the grid inverter at that time.
Carry out the System Commissioning testing in System Commissioning > Additional Tests.

NOTE: If Reactive Power is required to be configured, preform the following procedure before step 6. Reactive Power must also be set in the SP PRO that is connected to the ABB UNO.

    • Scroll to Reactive Power setting and press ENTER.
Image Placeholder

    • The ABB UNO “Reactive Power” consists of four types of management to enable. Set the appropriate parameters required, press the ENTER key to configure and return to the Settings menu.
Image Placeholder

Image Placeholder


System Commissioning  Additional Tests

In addition to the normal system testing that would be performed, the following additional tests must be performed as detailed below.


Communications Link Verification

The correct operation of the ABB Managed AC Coupling relies on the Communications Link. It is vital that the communications link (RS485) connection has been setup correctly before operating the AC coupled system.

Image Placeholder

  • Check that all the RS485 connections have been connected correctly.

  • Isolate the AC and connect the DC supply to the ABB UNO. Make sure that the DC supply is pressent at the ABB UNO and its display is on.

  • Using SP LINK, connect to the SP PRO. In the Data View > Now tab there should be a model number displayed for each of the installed inverters.

The communication link may be further tested using the AC Solar Link Test found in SP LINK under the Service Settings tab.

  • In the Service Settings tab click the Reset Counters button.
Image Placeholder

  • Wait 2 minutes and check that the error count remains at zero for all the connected ABB UNOs. (An error count of 3 or less per minute is acceptable but in this case, it is good practice to check the wiring and that the termination resistors are set correctly in the SP PRO and ABB UNO.

Once the Communications link has been verified for each ABB UNO, the AC feeds to each ABB UNO can be switched on and full system testing and verification can be performed.


Testing the failsafe on the RS485 Link

Once the system is operational, unplug the RS485 communications link from the SP PRO to the ABB UNOs. Wait 1 minute and check that the output of each of the ABB UNOs has dropped to approximately 0.1kW.



Appendix III: Communications Link Configuration for ABB DM PLUS with “AC Coupled Interface PCA”


The communication link always starts at the SP PRO and links to the “AC Coupled Interface PCA”, then connects to all the ABB UNOs in a daisy chain arrangement and finishes at the last ABB UNO. The ABB UNO link is used to connect subsequent ABB UNOs ON the same phase as the SP PRO. Do Not Connect ABB UNOs on different phases together.

To install the AC Coupled Interface PCA, remove the bottom two screws from the Expansion Card and replace them with the provided 2x standoffs. Then mount the AC Coupled Interface PCA to the Expansion Card inside the SP PRO close to the Serial Communication PCA as illustrated.

Image Placeholder
  • Connect the RJ45 Connector lead from the AC Coupled Interface PCA To RS485 Port 2 to the SP PRO Serial Communication PCA RS485 Port 2.

  • Connect the second RJ45 lead from the AC Coupled Interface PCA To ABB AC Coupled Inverter to the ABB UNO RS485 connector (see section “RS485 Connection to first ABB UNO”).

  • Connect the AC Coupled Interface PCA power loom (12V) from AC Coupled Interface PCA 12V DC Power J4 to the SP PRO Serial Communication PCA 12V connector.

NOTE: Do not connect any RJ45 leads to the AC Coupled Interface PCA To Other AC Coupled Inverters connector as the pin out is different to the ABB UNO connection.


ABB UNO Communication link to SP PRO Communication Card

Image Placeholder
SP PRO Connections (inside unit)
RS485 Port 2 RJ45 connector to AC Coupled Interface PCA and to ABB UNO RS485B connector

RS485 Connection to First ABB UNO

Using the supplied ‘CAT5’ network cable connect one end to the AC Coupled Interface PCA “To ABB AC Coupled Inverter” on the SP PRO. At ABB UNO 01 (Address# 02), cut off the non- connected RJ45 connector, expose and crimp the wires using wire crimps or alternatively use a longer cable as required (not supplied) as outlined in the table below.

NOTE: For wireless RS485 communication (Order code: 005316) please refer to Appendix I.

Image Placeholder

NOTE: There are two different colour coding for RJ45 plugs, T568A and T568B, it is common that either colour code is used. To ensure correct connections please check that the RS485 RJ45 Adaptor pin # (see below table) corresponds to the ABB UNO RS485 Connection by buzzing out the lead before connecting it to the ABB UNO or the SP PRO.

Image Placeholder

Table 4: RS485 adaptor to ABB UNO connections and wire colours

RS485 RJ45 Adaptor pin #
Signal
T568A colour code
T568B colour code
ABB UNO RS485 Connection
1
GND
Green/White
Orange/White

2
GND
Green
Orange

3
RS485 - B
Orange/White
Green/White
+T/R (RS485)
4
GND
Blue
Blue

5
RS485 - A
Blue/White
Blue/White
-T/R (RS485)
6
GND
Orange
Green

7
RS485 - RTN
Brown/White
Brown/White
RTN (RS485)
8
GND
Brown
Brown

Connect the three wires from the CAT5 network cable to the ABB UNO connector, +T/R, -T/R and RTN. The RS485 terminals are located on the right-hand side edge of the connector as illustrated.

Image Placeholder

Connection of AC Coupled Interface PCA To ABB AC Coupled Inverter to ABB UNO RS485 connector, colour code T568A is shown above.

NOTE: Only the wires connected to the RS485 are used in ABB UNO.

The last ABB UNO of the daisy chain must be terminated provided jumper at the pins marked

120Ω TERM must be placed in the ON position as shown.

Image Placeholder

NOTE: When connecting multiple ABB UNOs together, the terminating jumper must be set to OFF 120Ω TERM for all ABB UNO except the last inverter of the daisy chain (ON).


Connecting ABB UNO link between Inverters 02 (Address# 03) to 05 (Address# 06)

The following configuration outlines the connection for multiple ABB UNOs to the first ABB UNO (ABB UNO 01). If only a single ABB UNO is installed, skip to the next section (CONFIGURATION  ADDITIONAL SETTINGS).

Inside the ABB UNO there is an RS485 black terminal block. The ABB UNO RS485 is designed to interface with multiple ABB UNOs in a daisy chain arrangement as shown below.
When looping an ABB UNO to another ABB UNO, the termination jumper must be set to OFF (away from ON). For the last ABB UNO, the termination jumper must be set to “ON”.

Image Placeholder